17 Analog Input/Output Option Board
17-24
CP2E CPU Unit Software User’s Manual(W614)
17-10Trouble Shooting
Trouble-shooting with Indicators
ERR
Indicator
Error
Probably
Cause
Correction
Auxiliary Area
Allocations
AD/DA function
Lit CPU Unit ser-
vice monitoring
error
Service from
the CPU Unit
was not com-
pleted within
the fixed inter-
val.
Check and cor-
rect the CPU
Unit’s operat-
ing environ-
ment. Check
serial commu-
nication setting.
A435.14,
A435.15 will be
OFF
AD/DA conversion will stop.
The analog input conver-
sion data stops refreshing
and the analog output con-
version output becomes 0V.
Option board
error
An error
occurred in the
Analog Option
Board.
Restart the
CPU Unit.
Replace the
Analog Option
Board if the
error recurs.
Two Analog
Option Boards
are installed.
Install one Ana-
log Option
Board only.
A353.13 will be
ON
Flashing Communica-
tion error
The communi-
cation between
PLC is out of
service
Check if PLC is
running nor-
mally.
A435.15 will be
OFF
AD/DA conversion will stop.
The analog input conver-
sion data stops refreshing
and the analog output con-
version output becomes 0V.
If the communication recov-
ers from error, the AD/DA
conversion will start again.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CP2E-N D Series and is the answer not in the manual?

Omron SYSMAC CP2E-N D Series Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CP2E-N D Series
CategoryComputer Hardware
LanguageEnglish

Related product manuals