Page 2 -
Delete
the
information
under
the
heading
GENERATOR,
and
substi-
tute'
the
follorlng
information.
GENERATOR
The
air
cooled
generator
produces 600Q,watts
of
direct
current.
The
voltage
is
either
115
or
230
volts,
as
indicated
on
the
plant
nameplate.
The
generator
is
directly
coupled
to
the
engine,
the
armature
turning
at
crankshaft
speed.
The
generator
field
is
compound
wound
and
has
two
interpole
coils
for
better
commutation. The
generator\iS
self-excited.
The armature
is
supported
at
the
inner
end
by
the
engine
rear
ma:in
bear-
ing,
and
at
the
outer
end
by
a
large
ball
bearing.
An
extremely
large
commutator
is
mounted
at
the
ball
bearing
end
of
the
armature.
All
generator
windings
are
thoroughly
impregnated
with
in-
sulating
varnish
and baked,
to
minimize
the
possibility
of
internal
short
circuits.
'
A
ce~trifugal
weight
type,
gear
driven
governor
controls
the
speed
of
the
engine,
and so
the
output
voltage
of
the
generator.
The normal
speed
is
approximately
1800
r.p.m.
CONTROLS
Automatic
or
line
transfer
equipment
is
not
available
for
the
DC
plants.
Pages 4 and 5
-'Delete
the
information
under
the
subject
WIRING,
and
substitute
the
following
information.
BATTERIES.-
Two
6-volt
batteries
are
connected
in
series
by
a
short
jumper
cable.
Conne~t
the
cable
which
is
attached
to
the
start
solenoid
switch
to
the
remaining
positive
(+)
post
of
the
two
batteries.
Connect
the
cable
which
is
grounded on
the
cylinder
head
to
the
remaining
nega-
tive
(-)
post.
If
the
plant
was
boxed
for
export
shipment,
service
the
batteries
as
directed
on
the
tags
attached
to
the
batteries.
GROmmING.-
If
grounding
is
called
for
in
local
underwriters
I codes,
or
radio
interference
requires
it,
drive
a
1/2
11
diameter
pipe
or
rod
into
the
ground
as
,close
to
the
plant
as
is
practicable.
This
pipe
must
pene-
trate
moist
ground.
Fasten
an approved ground clamp
to
this
pipe,
and
run a number 8
or
larger
insulated
wire
from
the
clamp
to
the
negative
output
terminal
post
on
the
plant.
.
WIRING.-
Observe any
applicable
underwriters'
codes
when
connecting
the
load
wires
to
the
plant.
Use
sufficiently
large,
insulated
wire.
The
size
of
the
wire
depends upon
the
distance
and
permissible
voltage
drop
between
the
load
and
the
plant,
and
the
amount and kind'
of
the
load.
Connect
the
positive
wire
of
the
main
line
to
the
positive
( .. )
DC
OUTPUT
terminal
located
behind
the
control
panei.
Connect
the
negative
wire
of'
ttte
main
line
to
the
negative
(-)
DC
OUTPUT
terminal.
Some
model
plants
are
equipped
witJ::[
a duplex
receptacle
mounted upon
the,
control
panel,
which
may
be
used
to
connect a
load
not
to
exceed
15
amps.
at
115
volts,
or
10 amps.
at
230
volts
for
each
outlet.
If
the
plant
is
not
equipped
with
a
circuit
brefl;ker,
install
a
switch
in
the
main
line
as
close
to
the
plant
as
is
practicable.
r

Questions and Answers: