TABLE
1
UR GENERATOR VOLTAGE/CURRENT
OPTIONS
75 kW 93.75 kVA
DOUBLE
SERIES
PARALLEL
SERIES
REF
VOLTAGE
VOLTS
FREQ
PHASE AMPERES
DELTA
DELTA WYE
WYE
WIRE
(W12) TAP
110/220 50
Hz
1
355*
X
H6
115/230
50
Hz
1
340*
x H6
120/240 60
Hz
1
391*
X
H5
110/190
50
Hz
3
237
.
X
H3
115/200
50
Hz
3
226
X
H4
120/208 50
Hz
3
217
X
H4
120/208 -60
Hz
3
260
X
H3
110/220 50
Hz
3
205
X
H6
127/220 50
Hz
3
205
X
H5
127/220 60
Hz
3
246
X
H4
115/230 50
Hz
3
196
X
H6
120/240
60
Hz
'3 226
X
H5
139/240 60
Hz
3
226
X
H5
220/380 50
Hz
3
119
X
H3
230/400 50
Hz
3
113
*
X
H4
240/416 50
Hz
3
.
108
X
H4
240/416
60
Hz
3
130
X
H3
254/440
50
Hz
3
103
X
H5
254/440
60
Hz
3
123
X
H4
277/480
60
Hz
3
113
X
H5
9X
H5—Not
347/600 60
Hz
3
90
Reconnectible
This current value
is
available only from special long stack units (option B125).
A standard
3-phase
generator connected into
a
Double Delta configuration will deliver
2/3
current
value shown (355 x .66
=
237 amperes).
TABLEIA
UR GENERATOR VOLTAGE/CURRENT
OPTIONS
90
kW
75
kW
112.5
kVA
93.75
kVA
DOUBLE
SERIES
PARALLEL
SERIES
REF
VOLTAGE
VOLTS
FREQ
PHASE AMPERES
DELTA DELTA WYE WYE
WIRE
(W12) TAP
110/220 50
Hz
1
426*
X
H6
115/230 50
Hz
1
408*
X
H6
120/240 60
Hz
1
469*
X
H5
110/190
50
Hz
3
285
X
H3
115/200 50
Hz
3
271
X
H4
120/208
50
Hz
3
260
X
H4
120/208 60
Hz
3
312
X
H3
110/220
50
Hz
3
246
X
H6
127/220 50
Hz
3
246
X
H5
127/220
60
Hz
3
295
X
'
H4
115/230 50
Hz
3
235
X
H6
120/240
60
Hz
3
271
X
H5
139/240
60
Hz
3
271
X
H5
220/380
50
Hz
3
142
X
H3
230/400 50
Hz
3
135
X
H4
240/416 50
Hz
3
130
X
H4
240/416 60
Hz
3
156
.
X
H3
254/440
50
Hz
3
123
X
H5
254/440
60
Hz
3
148
X
H4
277/480 60
Hz
3
135
X
H5
9X
H5—Not
347/600
60
Hz
3
108 Reconnectible
This current value
is
available only from special long stack units (option B125).
A
standard
3-phase
generator connected into
a
Double Delta configuration will deliver
2/3
current
value shown
(426 x .66 =
284 amperes).