12
4. SPECIFICATIONS
4.1 Electrical Specifications
Product
Name
Frequency
(Hz)
Rated Voltage
(V)
VA / W
Capacity
100 / 110 / 120V
ES550C 50/60
220 / 230 / 240V
550/330
100 / 110 / 120V
ES800C 50/60
220 / 230 / 240V
800/480
100 / 110 / 120V
ES1000C 50/60
220 / 230 / 240V
1000/700
100 / 110 / 120V
ES1500C 50/60
220 / 230 / 240V
1400/980
100 / 110 / 120V
ES1000C-RM 50/60
220 / 230 / 240V
1000/700
100 / 110 / 120V
ES1500C-RM 50/60
220 / 230 / 240V
1400/980
Input Voltage Range
Upper Limit
Rated Voltage+25%
Buck
Rated Voltage+12.5%
Boost
Rated Voltage-12.5%
Lower Limit
Rated Voltage-25%
Input/Output Frequency
Input (AC mode)
45Hz – 55 Hz / 55 Hz – 65 Hz
Output (Inverter mode)
50 Hz / 60 Hz ± 0.1 Hz
Wave Form
AC Mode
sine wave
Back Up Mode
step wave
Transfer time
Power Failure AC Inverter
4 ms (typical)