Operation Manual
Circulation-Type Liquid Cooler
ORION Unit Cooler
RKS400F-S
RKS500F
RKS750F
CAUTION
This cooler is designed for industrial use. Handle with care.
Please read this manual carefully and operate this equipment
accordingly.
Retain this manual for future reference.
The product warranty is printed at the end of this manual.
Be sure to keep it in a safe place.
This manual is comprised of two sections.
Operation Guide ················· Pages 1 -
Installation Guide ············· Pages 37 -
*Photo: RKS750F
03107377010

Questions and Answers

  • J
    joelkellerAug 2, 2025
    What to do if my Orion RKS400F-S Accessories cooler is running but the cooling isn't good?
    • M
      Michael DodsonAug 3, 2025
      If the Orion Accessories cooler is running but the cooling capacity is poor, check for a gas leak. If the load is too great, reduce it. If the ambient temperature is too high, lower the cooler ambient temperature to below 40.
  • B
    beanmichelleAug 7, 2025
    How to fix an Orion RKS400F-S Accessories product that doesn’t run and the operation lamp is off?
    • A
      Angela ThomasAug 7, 2025
      If the Orion Accessories product doesn’t run and the Operation lamp remains off, the controller may be defective, so replace the controller. Also, the protective device may be defective (refer to protective-device explanations on the next page) or the fuse may be blown, so replace the fuse.
  • L
    Lauren OconnellAug 11, 2025
    What to do if the Orion RKS400F-S operation lamp is on, but the compressor isn't running?
    • L
      lmayAug 11, 2025
      If the Orion Accessories operation lamp is on, but the compressor is not running, ensure that the power voltage is at the rated level. If the voltage is correct, the electromagnetic contactor might be bad, and you should replace it.
  • I
    ijacksonAug 15, 2025
    What does the C07 warning on my Orion RKS400F-S mean?
    • G
      gwilsonAug 15, 2025
      If you receive a C07 - Water temp high/low warning on your Orion Accessories, and the water temperature does not fall to the set temperature, clean the condenser filter and/or reduce the ambient temperature and reduce the load. If the water temperature drops too low when the heat load is low, the temperature may drop 2.0 below the set temperature. There is no problem with the product as long as the temperature rises up again to the set temperature. The warning will automatically be canceled when the water temperature returns to within the set temperature range.
  • H
    hector84Aug 20, 2025
    What does error E09 on my Orion Accessories mean?
    • N
      Nicole GuerraAug 20, 2025
      The R phase is open. Check the power supply and fuse of your Orion Accessories.
  • D
    Denise LeeAug 25, 2025
    What does error E10 on my Orion Accessories mean?
    • E
      ecrosbyAug 25, 2025
      The power supply R, S, and T lines don't match up. Reverse 2 of the 3 lines of the power supply cable of your Orion Accessories.
  • J
    John ShannonAug 28, 2025
    What does the C00 error mean on my Orion Accessories?
    • P
      Patrick VelezAug 28, 2025
      If you are getting a 'C00 - Condenser (filter) inspection warning' on your Orion Accessories, clean the condenser (filter) if it is dirty and then press the reset switch for approximately 5 seconds.

Summary

Safety Precautions

Warning Symbols

Explains the meaning of hazard, prohibition, and mandatory safety symbols.

Operation Guide

Essential Safety Precautions

Provides crucial warnings and cautions for safe operation.

Machine Layout and Control

Details external components and the control panel interface.

Operating Procedures

Guides users through startup, normal, remote, and dual mode operations.

Maintenance and Troubleshooting

Inspection and Maintenance Schedule

Outlines weekly, monthly, and half-yearly inspection and maintenance tasks.

Water Quality Management

Provides guidelines for maintaining water quality to prevent damage.

Troubleshooting and Alarm Handling

Covers common issues, error codes, and safety device activations.

Installation Guide

Installation Site and Safety

Covers essential safety precautions and site selection criteria.

Piping and Wiring Installation

Details correct procedures for water piping and electrical wiring connections.

Specifications and Dimensions

Model Specifications

Lists technical data for RKS400F-S, RKS500F, and RKS750F models.

External Dimensions

Shows physical dimensions and port locations for each model.

Wiring Diagrams

Model-Specific Wiring

Provides detailed wiring diagrams for RKS400F-S, RKS500F, and RKS750F.

Product Warranty

Warranty Terms and Conditions

Details the warranty period, coverage, exclusions, and limitations.