47
Installation
Wiring Work
■Setting Up to Use Remote Operation and External Signals
The product accepts input of a remote-control drive signal, and generates output of a drive signal and
alarm signal. If you wish to use these signals, please refer to the specifications below and connect up
the wiring accordingly. Terminals should be fixed with M3.5 screw hardware.
1. Terminal specifications are shown as below.
Remote-Control Input
Non-voltage contact input (toggle switch)
Maximum cable length : 20m
Maximum impedance when shorted : 1k
Minimum impedance when open : DC11V ~ 18V
Inflow current : Approx. DC10mA ~ 17mA
Signal Output
Relay Output :“a” (normally-open) contacts
AC250V/DC30V 3A (resistance load)
Minimum allowable current (reference value) DC5V
10mA
2. Remote operation, signal output terminal specifications are shown as below.
Remote-Control Terminals
Signal-Output Terminals Remote Operation
Operation Signal
(Closed when cooler is running.)
Alarm sSgnal
(Closed to indicate ALARM condition.)