FAULTS UNRELATED TO THE REGULATOR
Stiff valve
Uneven temperature
Not enough heat
Clean the valve axle and the hole of the lid ange, and replace the O-rings of the axle with new ttings
or replace the valve. (Note! This work is usually performed by a plumber)
If the oor heating drainage water level is too high, the oor heating thermostats may prevent normal
circulation of water operated by the control valve. Reduce the level of drainage water to a minimum.
Ensure that there is enough heat available (i.e. boiler or accumulator temperature must be higher than
drainage water temperature). Also, ensure that the piping pressure level is sufcient and that the cir-
culation pump is running.
Tolerance ± 0,2 °C (0-70 °C)
Resistance value table NTC10
°C
-50
-40
-30
-25
-20
-15
-10
-5
672 600
337 270
177 210
130 540
97 140
72 990
55 350
42 340
Ω °C
0
5
10
15
20
25
30
35
Ω
32 660
25 400
19 900
15 710
12 490
10 000
8 055
6 531
°C
40
45
50
55
60
65
70
75
Ω
5 325
4 368
3 602
2 987
2 488
2 084
1 753
1 482
°C
80
85
90
95
100
110
120
130
140
Ω
1 257
1 072
917,4
788,2
679,8
511,0
389,4
300,5
234,7
HINTS FOR FIRST-TIME USE
If room temperature measurement is not in use: At rst the radiator thermostats should be turned fully open. Set the ne adjust-
ment so that the rst time there is below freezing temperatures outdoors, the room temperature stays about 1 °C higher than what
you want it to be. After that turn down the radiator thermostats just enough to obtain the desired room temperature. This prevents
the room temperature from dropping on windy days, because the radiator thermostats will be able to increase the heating level.
Room temperature measurement in use: Room control can, if necessary, raise or lower the temperature level of the whole house
and so the small temperature increase in the network mentioned before is not needed. Also you get more even temperature con-
trol in houses with oor heating when room temperature measurement is taken into use.
Warranty: Ouman Oy has given EH-800 a three year warranty for the device. The warranty covers repair of the device at Ouman
Oy:s factory and includes necessary spare parts. The warranty is not in effect if the device has been installed incorrectly or mechan-
ically damaged. The warranty does not cover indirect or consequential loss or damages. It does not cover the cost connected with
nding a fault, detaching the device, or sending or installing the device.
6/2013
OUMAN OY
Espoo sales office:
Upseerinkatu 1 Tel. +358 424 840 202
02600 Espoo Fax. +358 9 4780 1030
Factory and Oulu sales office:
Voimatie 6 Tel. +358 424 8401
90440 Kempele Fax. +358 8 815 5060
www.ouman.fi
ouman@ouman.fi
If the regulator is damaged, contact Ouman Oy. Send the damaged device via mail for factory
repair. Remove all plug connectors and diconnect the device from the valve. Remember to in-