EasyManua.ls Logo

Panasonic CS-E21DTES - How to Operate; Powerful & Quiet Operations; Fan Speed and Air Swing; Operating Hints

Panasonic CS-E21DTES
90 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.1. CS-E15DTEW CU-E15DBE
3 Product Specifications
Unit CS-E15DTEW CU-E15DBE
Cooling Capacity kW
kcal/h
BTU/h
4.15 (0.90 - 4.55)
3,570 (770 - 3,910)
14,200 (3,070 - 15,500)
Heating Capacity kW
kcal/h
BTU/h
5.17 (0.90 - 6.30)
4,450 (770 - 5,420)
17,600 (3,070 - 21,500)
Moisture Removal l/h
Pint/h
2.4
(5.1)
Power Source (Phase, Voltage, Cycle) ø
V
Hz
Single
230 - 240
50
Airflow Method OUTLET
INTAKE
SIDE VIEW TOP VIEW
Air Volume Lo m
3
/min (cfm) Cooling; 9.1 (320)
Heating; 8.3 (290)
Me m
3
/min (cfm) Cooling; 10.6 (370)
Heating; 10.4 (360)
Hi m
3
/min (cfm) Cooling; 12.0 (420) Cooling; 48.5 (1,710)
Heating; 12.2 (430) Heating; 48.5 (1,710)
dB (A) Cooling; High 45, Low 37 Cooling; 46
Heating; High 45, Low 33 Heating; 47
Noise Level
Power level dB Cooling; High 58 Cooling; High 59
Heating; High 58 Heating; High 60
Electrical Data Input Power W Cooling; 1,290 (255 - 1,550)
Heating; 1,550 (260 - 2,050)
Running Current A Cooling; 6.0 - 5.9
Heating; 7.1 - 7.0
EER W/W Cooling; 3.22 (3.53 - 2.94)
BTU/hW Cooling; 11.0 (12.0 - 10.0)
COP W/W Heating; 3.34 (3.46 - 3.07)
BTU/hW Heating; 11.4 (11.8 - 10.5)
Starting Current A 7.1
Piping Connection Port
(Flare piping)
inch
inch
G ; Half Union 1/2
L ; Half Union 1/4
G ; 3-way valve 1/2
L ; 2-way valve 1/4
6
CS-E15DTEW CU-E15DBE / CS-E18DTEW CU-E18DBE / CS-E21DTES CU-E21DBE

Table of Contents

Other manuals for Panasonic CS-E21DTES

Related product manuals