17
Indoor CS-E24PKEW CS-E28PKES
Model
Outdoor CU-E24PKE CU-E28PKE
Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 15.88 (5/8) 6.35 (1/4) / 15.88 (5/8)
Standard length m (ft) 5.0 (16.4) 5.0 (16.4)
Length range (min – max) m (ft) 3 (9.8) ~ 30 (98.4) 3 (9.8) ~ 30 (98.4)
I/D & O/D Height different m (ft) 20.0 (65.6) 20.0 (65.6)
Additional Gas Amount g/m (oz/ft) 30 (0.3) 30 (0.3)
Piping
Length for Additional Gas m (ft) 10 (32.8) 10 (32.8)
Inner Diameter mm 16.7 16.7
Drain Hose
Length mm 650 650
Fin Material Aluminium (Pre Coat) Aluminium (Pre Coat)
Fin Type Slit Fin Slit Fin
Row × Stage × FPI 2 × 17 × 21 2 × 17 × 21
Indoor Heat
Exchanger
Size (W × H × L) mm 836.5 × 357 × 25.4 836.5 × 357 × 25.4
Fin Material Aluminium Aluminium
Fin Type Corrugated Fin Corrugated Fin
Row × Stage × FPI 2 × 30 × 19 2 × 30 × 19
Outdoor
Heat
Exchanger
Size (W × H × L) mm 38.1 × 762 × 895.8:865.8 38.1 × 762 × 895.8:865.8
Material Polypropelene Polypropelene
Air Filter
Type One-touch One-touch
Power Supply Indoor Indoor
Power Supply Cord A Nil Nil
Thermostat Electronic Contol Electronic Contol
Protection Device Electronic Contol Electronic Contol
Dry Bulb Wet Bu b Dry Bulb Wet Bu b
Maximum °C 32 23 32 23
Cooling
Minimum °C 16 11 16 11
Maximum °C 30 – 30 –
Indoor
Operation
Range
Heating
Minimum °C 16 – 16 –
Maximum °C 43 26 43 26
Cooling
Minimum °C -10 – -10 –
Maximum °C 24 18 24 18
Outdoor
Operation
Range
Heating
Minimum °C -15 -16 -15 -16
1. Cooling capacities are based on indoor temperature of 27°C Dry Bulb (80.6°F Dry Bulb), 19.0°C Wet Bulb (66.2°F Wet Bulb) and outdoor air
temperature of 35°C DRY BULB (95°F Dry Bulb), 24°C Wet Bu b (75.2°F Wet Bulb)
2. Heating capacities are based on indoor temperature of 20°C Dry Bulb (68°F Dry Bu b) and outdoor air temperature of 7°C Dry Bulb (44.6°F
Dry Bu b), 6°C Wet Bulb (42.8°F Wet Bulb)
3. Heating low temperature capacity, Input Power and COP measured at 230 V, indoor temperature 20°C, outdoor 2/1°C
4. Heating extreme low temperature capacity, Input Power and COP measured at 230 V, indoor temperature 20°C, outdoor -7/-8°C
5. Standby power consumption ≤0.7w (when switched OFF by remote control, except under self protection control).
6. Specifications are subjected to change without prior notice for further improvement.