82
[Heating]
• According to indoor pipe temperature, automatic heating fan speed is determined as follows.
B. Feedback control
• Immediately after the fan motor started, feedback control is performed once every second.
• During fan motor on, if fan motor feedback ≥ 2550 rpm or < 50 rpm continue for 10 seconds, then fan motor error
counter increase, fan motor is then stop and restart. If the fan motor counter becomes 7 times, then H19 - fan
motor error is detected. Operation stops and cannot on back.
13.3 Outdoor Fan Motor Operation
• It starts when compressor starts operation and it stops 30 seconds after compressor stops operation.
• During cooling operation, and outdoor ambient temperature is below 8°C, outdoor fan speed will be controlled
according to outdoor piping temperature as following:
OD Pipe Temperature
A 26°C
B 33°C
• During above condition, when indoor heat exchanger temperature is below 5°C, the outdoor fan will stop
according to outdoor piping temperature as following: