13.3.1.5  Low Pressure Prevention Control (Gas Leakage Detection) 
•  Control start conditions 
o  For 5 minutes, the compressor continuously operates and outdoor total current is between 1.5A and 1.88A. 
o  During Cooling and Soft Dry operations: 
  Indoor heat exchanger temperature is above 20°C. 
o  During heating operations: 
  Indoor heat exchanger temperature is below 25°C. 
 
• Control contents 
o  Compressor stops (and restart after 3 minutes). 
o  If the conditions above happen 2 times within 20 minutes, the unit will: 
 Stop operation 
  Timer LED blinks and “F91” indicated (Refrigeration cycle abnormality). 
 
13.3.1.6  4-Way Valve Failure Protection Control 
•  During Cooling operation 
o  4 minutes after compressor started, if the temperature of the indoor unit heat exchanger exceeds 45°C, the 
compressor stops (After 3 minutes, Time delay safety control starts). 
o  If this situation occurs 4 times within 30 minutes, TIMER LED blinks (F11 error) 
•  During Heating operation 
o  4 minutes after compressor started, if the temperature of the indoor unit heat exchanger drops below 5°C, 
the compressor stops (After 3 minutes, Time delay safety control starts). 
o  If this situation occurs 4 times within 30 minutes, TIMER LED blinks (F11 error) 
 
13.3.2  Protection Control for Cooling & Soft Dry Operation 
13.3.2.1  Cooling overload control 
•  Detects the outdoor pipe temperature and carry below restriction/ limitation (limit the compressor operation 
frequency). 
•  If the outdoor heat exchanger temperature exceeds 52°C during cooling / dry operation, the compressor 
frequency is restricted. 
•  If the compressor if outdoor pipe temperature exceeds 62°C. 
•  If the compressor stops 4 times within 20 minutes, TIMER LED blinks (F95: outdoor high pressure rise 
protection)