8 Operation Details
8.1 .Cooling Mode Operation
Whenselecting the Cooling Mode Operation, the unit will operate according to the setting by the RemoteController or
the control panel onthe indoor unit and theoperationisasthe following.
Time Delay Safety Con trol
3 min.----If the compressor stops, itwill not restart within 3 minutes.(Protection of compressor).
7 Minutes Time Save Control
7 min.----The unitwill automatically operate in 7 minutes even if the room temperature is not reached.
(Prevention of raising the humidity)
Evaporator
Temperature
()
10
2
Restart
4 minutes
Compressor ceases
Time
Anti-Freezing Control
If temperature of evaporator is lower than 2 continuously
for 4 minutes, the compressor will cease to prevent the
evaporator from freezing.Fan speed setting will not be
changed.
When temperature of evaporator reaches 10 ,compressor
will restart.
During Cooling Mode Operation, the Time Delay Safety
Controlisavailable.
Indoor Fan
STOP
Slow
Slow
STOPSTOP
SlowSlow
STOP
ON
Compressor
ON
1 Fan speed will be at Hi till the compressor ceases(settemperature reached).
2 Fan speed will be at Me whenthe c ompressor restarts.
40 30 40 3020 160
1
2
Automatic Fan Speed Mode
During Cooling Mode Operation, use remote controller to select Automatic Fan Speed.
Deodorization control.
Fan speed will be at the point between "High speed"and "Medium speed".
CS-PV9DKE / CU-PV9DKE / CS-PV12DKE / CU-PV12DKE