11.2  Indoor Fan Motor Operation 
11.2.1  Basic Rotation Speed 
• Manual Fan Speed 
o  Fan motor’s number of rotation is determined according to remote control setting. 
 
Remote control  ○  ○  ○  ○  ○ 
Tab Hi Me+ Me Me- Lo 
•  Auto Fan Speed 
o  According to room temperature and setting temperature, indoor fan speed is determined automatically. 
o  The indoor fan will operate according to pattern below. 
 
Fan Speed a b c d e f  g h a b  
    
Higher 
   
Medium 
  
Lower 
   
   [1 pattern : 10s]   
• Feedback control 
o  Immediately after the fan motor is started, feedback control is performed once every second. 
o  During fan motor on, if fan motor feedback ≥ 2550 rpm or <50 rpm continuously for 10 seconds, the fan motor 
error counter increased; fan motor is then stopped and restarted. If the fan motor error counter increased to 7, 
then H19 – fan motor error is detected. Operation stopped and could not be restarted. 
11.3  Outdoor Fan Motor Operation  
Outdoor fan motor is operated with one fan speed only. Outdoor fan turns on when compressor starts to operate. But 
outdoor fan will turns off 30 seconds after compressor stops to operate. 
 ON     ON 
Compressor     OFF   
 ON Fan Speed   ON 
Outdoor Fan    30 sec OFF  
11.4 Airflow Direction 
•  There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by 
vertical vanes). 
•  Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat 
exchanger temperature and intake air temperature) and manual (angles of direction can be adjusted using 
remote control). 
 
11.4.1 Vertical Airflow 
Vane Angle (°) 
Operation Mode  Airflow Direction 
1 2 3 4 5 
Auto  20 ~ 45 
Cooling and e-ion 
Manual  20 26 32 37 45 
Auto  20 ~ 45 
Soft Dry 
Manual  20 26 32 37 45 
 
•  Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the 
angles as stated above. When the air conditioner is stopped using remote control, the vane will shift to close 
position. 
•  Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and 
the positions of the vane are as figure below. When the air conditioner is stopped using remote control, the vane 
will shift to close position.  
 
 
 
 
 
 
 
Side View 
1 
2 
3 
4 
5 
140° 
Close position