43 
14.2  Breakdown Self Diagnosis Function 
14.2.1  Self Diagnosis Function (Three Digits Alphanumeric Code) 
•  Once error occurred during operation, the unit will stop its operation, and Timer LED blinks. 
•  Although Timer LED goes off when power supply is turned off, if the unit is operated under a breakdown 
condition, the LED will ON again. 
•  In operation after breakdown repair, the Timer LED will not blink. The last error code (abnormality) will be stored 
in IC memory. 
14.2.2  To Make a Diagnosis 
1  Timer LED starts to blink and the unit automatically stops the operation. 
2  Press the CHECK button on the remote control continuously for 5 seconds. 
3  “- -“ will be displayed on the remote control display.  
Note: Display only for “- -“ (No signal transmission, no receiving sound and 
no Power LED blinking) 
4  Press the TIMER ▲ or ▼ button on the remote control. The code “H00” (no 
abnormality) will be displayed and signal will be transmit to the main unit. 
5  Each press of the button (▲ or ▼) will increase error code number and 
transmit error code signal to the main unit. 
6  When the latest abnormality code on the main unit and code transmitted 
from the remote control are matched, Power LED will light up for 30 
seconds and a “beep” sound (continuously for 4 seconds) will be heard. If 
no codes are matched, Power LED will light up for 0.5 seconds and no 
sound will be heard. 
7  The breakdown diagnosis mode will be canceled unless pressing the 
CHECK button continuously for 5 seconds or operating the unit for 30 
seconds. 
8  The LED will be off if the unit is turned off or the RESET button on the main 
unit is pressed. 
14.2.3  To Display Memorized Error Code (Protective Operation) 
1  Turn power on. 
2  Press the CHECK button on the remote control 
3  “- -“ will be displayed on the remote control display. 
Note: Display only for “- -“ (No signal transmission, no receiving sound and no Power LED blinking) 
4  Press the TIMER ▲ or ▼ button on the remote control. The code “H00” (no abnormality) will be displayed 
and signal will be transmit to the main unit. 
5  Each press of the button (▲ or ▼) will increase error code number and transmit error code signal to the main 
unit. 
6  When the latest abnormality code on the main unit and code transmitted from the remote control are matched, 
Power LED will light up for 30 seconds and a “beep” sound (continuously for 4 seconds) will be heard. If no 
codes are matched, Power LED will light up for 0.5 seconds and no sound will be heard. 
7  The breakdown diagnosis mode will be canceled unless pressing the CHECK button continuously for 5 
seconds or operating the unit for 30 seconds. 
8  The same diagnosis can be repeated by turning power on again. 
14.2.4  To Clear Memorized Error Code after Repair (Protective Operation) 
1  Turn power on (in standby condition). 
2  Press the AUTO button for 5 seconds (a “beep” sound is heard) on the main unit to operate the unit at 
Forced Cooling Operation Mode. 
3  Press the CHECK button on the remote control for about 1 second with a pointed object to transmit signal to 
main unit. A “beep” sound is heard, and the Error Code is cleared. 
14.2.5  Temporary Operation (Depending On Breakdown Status) 
1  Press the Auto OFF/ON button on the main unit (a “beep” sound is heard) to operate the unit. (Remote 
control is enable again). 
2  The unit can be temporarily be used until repaired. 
Error Code  Operation  Temporary items 
H23 Cooling 
H27, H28  Cooling 
Emergency Operation 
with limited power