•  Remote Control Receiving Sound 
o Normal Operation    Î e-ion Operation    : Beep 
o e-ion Operation     Î Normal Operation    : Beep 
o  Stop  Î e-ion individual Operation  : Beep 
o  e-ion individual Operation  Î Stop    : Long Beep 
 
• Power failure 
o  During e-ion individual operation, if power failure occurs, after power resumes, e-ion individual operation 
resumes immediately. 
o  During combination operation, if power failure occurs, after power resumes, combination operation resume 
immediately. 
o  e-ion operation status is not memorized after OFF the unit. After OFF, when the operation is ON again, air 
conditioner operates without e-ion operation. 
 
• e-ion Check Mode 
o  To check if e-ion is malfunctioning, press “e-ion” button and then follow by “Check” button to enter e-ion 
Check Mode and supplies power to the Active e-ion Air Purifying System. 
o  If abnormal discharge is detected at filter (short-circuited) due to water or dust adhesion, etc., the e-ion 
indicator blinks immediately. 
 
•  Error Detection Control 
When e-ion indicator blink, it indicates error listed below: 
o  Active e-ion Air Purifying system PCB main connector open: 
 Judgment Method 
•  During e-ion operation (include during Patrol operation), Active e-ion Air Purifying system main 
connector to PCB is opened. 
 
 Troubleshooting Methods 
•  Connect the connector or stop operation (include during Patrol operation) to cancel the blinking. 
 
o  Abnormal Discharge error: 
 Judgment Method 
•  During e-ion operation, feedback voltage is-Lo (at microcontroller) is detected, it is judged abnormal 
discharge and stops power supplies to the Active e-ion Air Purifying system. 
•  Abnormal discharge is caused by ionizer or filter’s high voltage power supply short-circuits due to 
water or dust adhesion, and so forth. 
•  When abnormal discharge occurred, every 30 minutes the unit supplies power to the Active e-ion Air 
Purifying system. 
•  When abnormal discharge occurs for 24 times continuously, e-ion indicator blinks (not applicable for 
e-ion Check Mode, where the error will shows immediately despite the 24 times counter) 
 
 Troubleshooting Method 
•  Press “e-ion” button or “OFF/ON” button to stop the operation and check the Active e-ion Air 
Purifying system main connector to PCB. 
•  After that, press “e-ion” button again to confirm the e-ion indicator not blinking. 
•  The 24 times counter will be clear after 10 minutes of normal operation or when operation stops. 
 
 Error Reset Method 
•
  Press “OFF/ON” button to OFF the operation. 
•  Press AUTO OFF/ON button at indoor unit to OFF the operation. 
•  OFF Timer activates 
•  Press “e-ion” button during e-ion individual mode. 
•  Power supply reset