57 
14.4.13    H58 (Patrol Sensor Abnormality) 
Malfunction Decision Conditions 
•  If Patrol sensor feedback is 0V or 5V continuous for 6 hours. 
•  Error will display only when the Patrol operation is ON. 
 
Malfunction Caused 
• Faulty connector connection. 
•  Faulty Patrol sensor. 
 
Troubleshooting 
 
NO 
When abnormality indication starts again 
• Defective Patrol sensor. 
• Re
lace the Patrol sensor. 
Has the error occurred after 6 hours continuous of 
PATROL ON function? 
Check at indoor PCB’s CN-DISP (14-15) and CN-DISP1 (1-2) 
connector. No loose cable or broken? 
  Correct loose or broken cable / 
connector. 
For safety reason and to prevent 
component breakdown, always switch 
off the power before remove and 
connect the component.