14.4.18    F90 (Power Factor Correction Protection) 
Malfunction Decision Conditions 
•  During startup and operation of cooling and heating, when Power Factor Correction (PFC) protection circuitry at 
the outdoor unit main PCB senses abnormal high DC voltage level. 
 
Malfunction Caused 
•  DC voltage peak due to power supply surge. 
•  DC voltage peak due to compressor windings not uniform. 
•  Faulty outdoor PCB. 
 
Troubleshooting 
 
 
YES  
When abnormality indication starts again 
Su
ecified? 
YES 
(~28Vdc) 
Correct the power supply 
Is the DC voltage between P (+) and N (-) terminal normal 
between 285~315Vdc)? 
Check the su
e 
Operate the system. Verify PFC abnormality by measuring DC 
voltage between P (+) and N (-) terminal at the outdoor unit PCB. 
Are the com
 
Check the compressor winding resistance: 
•  Turn off the power supply and disconnect the harness U, V 
and W. 
• Measure the windin
  Replace the compressor 
NO  
  Defect in PFC circuitry 
•  Replace the outdoor unit PCB 
NO 
NO  
YES  
•  Replace the outdoor unit PCB. 
For safety reason and to prevent 
component breakdown, always 
switch off the power before remove 
and connect the component.