134 
18. Troubleshooting Guide 
18.1  Refrigeration Cycle System 
In order to diagnose malfunctions, make sure that there are no 
electrical problems before inspecting the refrigeration cycle. 
Such problems include insufficient insulation, problem with the 
power source, malfunction of a compressor and a fan. 
The normal outlet air temperature and pressure of the refrigeration 
cycle depends on various conditions, the standard values for them 
are shown in the table on the right. 
 
 
 
 
 
 
 
 
 
 
Normal Pressure and Outlet Air Temperature (Standard)
 
Gas Pressure 
MPa 
(kg/cm
2
G) 
Outlet air 
Temperature 
(°C) 
Cooling Mode 0.9 ~ 1.2 (9 ~ 12)  13 ~ 17 
Heating Mode 2.0 ~ 2.7 (20 ~ 27)  32 ~ 42 
*Condition:  • Indoor fan speed = High 
• Outdoor temperature 35°C at the cooling 
                      mode and 7°C at the heating mode 
                    • Compressor operates at rated frequency