78 
12.5 Outdoor Unit 
  If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the 
condenser is not obstructed. 
  There should not be any animal or plant which could be affected by hot air discharged. 
  Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles. 
  Do not place any obstacles which may cause a short circuit of the discharged air. 
  If piping length is over the [piping length for additional gas], additional refrigerant should be added as shown in 
the table. 
 
Table A 
Model 
Capacity  
W (HP) 
Piping size 
Std.  
Length (m) 
Max  
Elevation (m)
Min. Piping 
Length (m) 
Max. Piping 
Length (m) 
Additional 
Refrigerant 
(g/m) 
Piping Length 
for add. gas 
(m) 
Max. 
Refrigerant 
Charge (kg) 
Indoor 
A
min
 (m
2
) 
Gas  Liquid 
TZ20***  3/4HP 
9.52 mm  
(3/8
") 
6.35 mm  
(1/4
") 
5 
15  3  15  10  7.5  0.60  Not applicable (*)
TZ25***, 
RZ25*** 
1.0HP  15  3  15  10  7.5  0.69  Not applicable (*)
TZ35***, 
RZ35*** 
1.5HP  15  3  15  10  7.5  0.75  Not applicable (*)
TZ42***  1.75HP 
12.7 mm  
(1/2
") 
15  3  15  10  7.5  0.87  Not applicable (*)
TZ50***, 
RZ50*** 
2.0HP  15  3  20  15  10  1.22  Not applicable (*)
TZ60***  2.25HP  15  3  30  15  10  1.52  Not applicable (*)
TZ71***  2.5HP 
15.88 mm 
(5/8
") 
20  3  30  25  10  1.85  4.46 
 
(*) Systems with total refrigerant charge, m
c
, lower than 1.84 kg are not subjected to any room area requirements. 
 
Example: For TZ20*** 
If the unit is installed at 10 m distance, the quantity of additional refrigerant should be 25 g .... (10-7.5) m x 10 g/m = 
25 g. 
 
A
min
 = (m
c
 / (2.5 × (LFL)
(5/4)
 × h
0
)) 
2
 
** not less than safety factor margin 
A
min
 
= Required minimum room area, in m
2
 
 
m
 
= Refrigerant charge in appliance, in kg   
LFL 
= Lower flammability limit (0.307 kg/m
)   
h
0
  = Installation height of the appliance (1.8 m for wall mounted) 
SF 
= Safety factor with a value of 0.75 
 
** The required minimum room area, A
min
, shall also be governed by the safety factor margin formula below : 
 
A
min
 = m
c
 / (SF × LFL × h
0
)   
The higher value shall be taken when determining the room area. 
12.5.1  Outdoor Unit Installation Diagram 
 
 
 
 
 
 
•
This illustration is for 
explanation purposes only.
It is advisable to avoid more 
than 2 blockage directions. 
For better ventilation & 
multiple-outdoor installation, 
please consult authorized 
dealer/specialist.
Installation parts you 
should purchase (
)
Connection cable ( )
1/4" Liquid side piping (
)
Gas side piping (
)
Additional drain 
hose (
)
100 mm 
or more
300 mm 
or more
1000 mm 
or more
100 mm 
or more