18.2  Breakdown Self Diagnosis Function 
18.2.1  Self Diagnosis Function (Three Digits Alphanumeric Code) 
  Once abnormality has occurred during operation, 
the unit will stop its operation, and Timer LED 
blinks. 
  Although Timer LED goes off when power supply 
is turned off, if the unit is operated under a 
breakdown condition, the LED will light up again. 
  In operation after breakdown repair, the Timer 
LED will no more blink. The last error code 
(abnormality) will be stored in IC memory. 
18.2.2  To Make a Diagnosis 
1  Timer LED start to blink and the unit 
automatically stops the operation. 
2  Press the CHECK button on the remote 
controller continuously for 5 seconds. 
3  “- -” will be displayed on the remote controller 
display. 
Note: Display only for “- -”. (No transmitting 
signal, no receiving sound and no Power LED 
blinking.) 
4  Press the “TIMER” ▲ or ▼ button on the 
remote controller. The code “H00” (no 
abnormality) will be displayed and signal will 
be transmitted to the main unit. 
5  Every press of the button (up or down) will 
increase abnormality numbers and transmit 
abnormality code signal to the main unit. 
6  When the latest abnormality code on the main 
unit and code transmitted from the remote 
controller are matched, power LED will light 
up for 30 seconds and a beep sound 
(continuously for 4 seconds) will be heard. If 
no codes are matched, power LED will light up 
for 0.5 seconds and no sound will be heard. 
7  The breakdown diagnosis mode will be 
canceled unless pressing the CHECK button 
continuously for 5 seconds or operating the 
unit for 30 seconds. 
8  The LED will be off if the unit is turned off or 
the RESET button on the main unit is pressed. 
18.2.3  To Display Memorized Error 
Code (Protective Operation) 
1  Turn power on. 
2  Press the CHECK button on the remote 
controller continuously for 5 seconds. 
3  “- -” will be displayed on the remote controller 
display. 
Note: Display only for “- -”. (No transmitting 
signal, no receiving sound and no Power LED 
blinking.) 
4  Press the “TIMER” ▲ or ▼ button on the 
remote controller. The code “H00” (no 
abnormality) will be displayed and signal will 
be transmitted to the main unit. The power 
LED lights up. If no abnormality is stored in 
the memory, three beeps sound will be heard. 
5  Every press of the button (up or down) will 
increase abnormality numbers and transmit 
abnormality code signal to the main unit. 
6  When the latest abnormality code on the main 
unit and code transmitted from the remote 
controller are matched, power LED will light 
up for 30 seconds and a beep sound 
(continuously for 4 seconds) will be heard. If 
no codes are matched, power LED will light up 
for 0.5 seconds and no sound will be heard. 
7  The breakdown diagnosis mode will be 
canceled unless pressing the CHECK button 
continuously for 5 seconds or operating the 
unit for 30 seconds. 
8  The same diagnosis can be repeated by 
turning power on again. 
 
 
18.2.4  To Clear Memorized Error Code 
after Repair (Protective 
Operation) 
1  Turn power on (in standby condition). 
2  Press the AUTO button for 5 seconds (A beep 
receiving sound) on the main unit to operate 
the unit at Forced Cooling Operation modes. 
3  Press the CHECK button on the remote 
controller for about 1 second with a pointed 
object to transmit signal to main unit. A beep 
sound is heard from main unit and the data is 
cleared. 
18.2.5  Temporary Operation (Depending 
On Breakdown Status) 
1  Press the AUTO button (A beep receiving 
sound) on the main unit to operate the unit. 
(Remote control will become possible.) 
2  The unit can temporarily be used until 
repaired. 
 
 
 
 
 
 
 
 