60 
12.2 Indoor Unit 
12.2.1  How to Fix Installation Plate 
The mounting wall shall be strong and solid enough to prevent it from vibration. 
 
 
 
Model 
Dimension 
1 2  3  4  5  6 
TZ20***, TZ25***, TZ35***, 
TZ42***, TZ50*** 
RZ25***, RZ35***, RZ50*** 
465 mm  70 mm ( * ) 365 mm  415 mm  60 mm  120 mm 
 
The center of installation plate should be at more than 1 at right and left of the wall. 
The distance from installation plate edge to ceiling should more than 2. 
From installation plate center to unit’s left side is 3. 
From installation plate center to unit’s right side is 4. 
○
B 
 :   For left side piping, piping connection for liquid should be about 5 from this line.
 :   For left side piping, piping connection for gas should be about 6 from this line. 
 
Dimension 2 
(*) :- 
If holder at the rear of chassis 
(Refer column “12.2.3 Indoor 
Unit Installation”) need to be 
used to prop up the unit, this 
distance shall be 85 mm or 
more. 
 
1  Mount the installation plate on the wall with 5 screws or more (at least 5 screws). 
(If mounting the unit on the concrete wall, consider using anchor bolts.) 
o  Always mount the installation plate horizontally by aligning the marking-off line with the thread and using 
a level gauge. 
2  Drill the piping plate hole with ø70 mm hole-core drill. 
o  Line according to the left and right side of the installation plate. 
The meeting point of the extended line is the center of the hole. 
Another method is by putting measuring tape at position as shown in the diagram above. 
The hole center is obtained by measuring the distance namely 115 mm for left and right hole respectively. 
o  Drill the piping hole at either the right or the left and the hole should be slightly slanting to the outdoor 
side. 
12.2.2  To Drill a Hole in the Wall and Install a Sleeve of Piping 
1  Insert the piping sleeve to the hole. 
2  Fix the bushing to the sleeve. 
3  Cut the sleeve until it extrudes about 15 mm 
from the wall. 
 
 
CAUTION
 
  
   When the wall is hollow, please be sure to use 
      the sleeve for tube assembly to prevent dangers 
  caused by mice biting the connection cable. 
 
4  Finish by sealing the sleeve with putty or 
caulking compound at the final stage. 
 
 
 
 
 
 
 
 
 
 
PIPE HOLE 
CENTER
115mm TO
HOLE CENTER
PIPE 
HOLE 
CENTER
115mm TO
HOLE CENTER
4
Installation 
plate 
1
2
 screw
More than 
1
More than 
1
Measuring Tape
Indoor unit
168 mm
115 mm
216 mm
115 mm
More 
than 
2
For best strength of 
INDOOR unit installation, 
it is highly recommended 
to locate “
” at 5 position 
as shown. 
3
5
6
4
Ceiling
Wall
Wall
15 mm
Putty or caulking compound
ø70 mm 
through hole
Indoor
Outdoor
Sleeve for tube 
assembly
Approx. 5 - 7 mm
Bushing for 
tube assembly
Wall