12.2.4 Connect the Cable to the Indoor Unit
The power supply cord, indoor and outdoor unit connection cable can be connected without removing the front
grille.
1 Install the indoor unit on the installing holder that mounted on the wall.
2 Open the front panel and grille door by loosening the screw.
3 Cable connection to the power supply through Isolating Devices (Disconnecting means).
o Connect the approved polychloroprene sheathed Power supply cord 3 x 1.5 mm
2
(3/4 ~ 1.75HP) or 3 x
2.5 mm
2
(2.0HP), type designation 60245 IEC 57 or heavier cord to the terminal board, and connect the
other end of the cable to Isolating Devices (Disconnecting means).
o Do not use joint power supply cord. Replace the wire if the existing wire (from concealed wiring, or
otherwise) is too short.
o In unavoidable case, joining of power supply cord between isolating devices and terminal board of air
conditioner shall be done socket and plug rated 15/16 A (3/4 ~ 1.75HP) or 16 A (2.0HP). Wiring work to
both socket and plug must follow to national wiring standard.
4 Bind all the Power supply cord lead wire with tape and route the power supply cord via the left side
escapement.
5 Connection cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 x
1.5 mm
2
(3/4 ~ 1.75HP) or 4 x 2.5 mm
2
(2.0HP) flexible cord, type designation 60245 IEC 57 or heavier cord.
6 Bind all the indoor and outdoor Connection cable with tape and route the connection cable via the right side
escapement.
7 Remove the tapes and connect the power supply cord and connection cable between indoor unit and outdoor
unit according to the diagram below.
PIPE
HOLE
CENTER
115mm TO
HOLE CENTER
•
How to pull the piping and drain hose out, in case of the
embedded piping.
•
In case of left piping how to insert the connection cable
and drain hose.
Rear view for left piping installation
Drain cap
Drain hose
Adjust the piping
slightly downwards.
Drain hose
Connection cable
Change the drain hose position
Sleeve for piping hole
Drain hose
Piping
Connection cable
More than 950 mm
Cable
45°
Drain hose
Piping
(For the right piping, follow the same procedure)
PVC tube for drain
hose
Indoor unit
55 mm
Piping
Cable
Apply putty or
caulking material
to seal the wall
opening.
Connection cable
Piping
More than
470 mm
More than
950 mm
PVC tube (VP-65) for piping
and connection cable
More than
700 mm
Drain hose
from main unit
PVC tube for drain hose (VP-30)
PVC tube for
drain hose (VP-20)
Tape
Power
upply
ord
Connection cable
Tape