Operation Details
Time Delay Safety Control (3 minutes)
7 minutes Time Saved Control
Anti-Freezing Control
Compressor Reverse Rotation
Protection Control
Compressor
restarts
(3 minutes waiting)
Compressor
OFF
➡➡
1) Cooling Mode Operation
Cooling in operation according to Remote Control setting.
When the compressor is stopped by Power Switch, Remote Control or there is a power failure, it restarts after 3
minutes when the Power Switch, Remote Control is turned ON or the power supply is resumed.
When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3
minutes.
The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is below the
compressor ON temperature.
After the compressor starts for 50 seconds but the outdoor fan motor is still OFF, the compressor will stop and
restart automatically. (Time Delay Safety Control is valid).
If the above phenomenon is repeated for 3 times, the compressor will stops.
The above phenomenon is reset when there is a change to heating mode or stopped by Remote Control Switch.
If the compressor is operating continually for 5 minutes or longer and the temperature difference between intake air
and indoor heat exchanger is 2.5°C or less for 2 minutes, compressor will stop and restart automatically.
(Time Delay Safety Control is valid).
T = intake air temperature – indoor heat exchanger temperature
This is to protect reverse rotation of the compressor when there is a instantaneous power failure.
If the temperature of the indoor heat exchanger
falls continously below 2°C for 4 minutes, the
compressor turns off to protect the indoor heat
exchanger from freezing. The fan speed setting
remains the same.
Compressor recommences when the indoor heat
exchanger temperature rises to 10°C (Recovery).
* 3 minutes waiting of Time Delay Safety
Control is valid for Cooling Operation.
Recovery
4 min
Compressor OFF
Indoor heat
exchanger
temperature
(°C)
2
10
Compressor
restarts
(3 minutes waiting)
Compressor
OFF
➡➡
Comp. operates for 50 secs.
and
Fan Motor OFF
Compressor Protection Control
Compressor starts for > 5 minutes
T 2.5°C for 2 minutes
Untitled-5 6/30/00, 7:54 AM17