SpecificationsFP0 A/D Converter Unit
7 3
7.1 Specifications
7.1 Specifications
General specifications
Item Description
Rated operation voltage 24V DC
Operating voltage range 21.6 to 26.4V DC
Rated current consumption 60mA or less (at 24V DC)
Current consumption increase of control unit
20mA or less (at 24V DC)
Allowable instantaneous stop time 10ms
Ambient temperature
0 to +55°C/32 to + 131°F
Storage temperature
20 to +70°C/4 to +158°F
Ambient humidity
30 to 85%RH (at 25°C noncondensing)
Storage humidity
30 to 85%RH (at 25°C noncondensing)
Breakdown voltage
500V AC for 1 minute between analog input terminal and power
supply/ground terminal
Insulation resistance
Min. 100MΩ (measured with a 500V DC megger) for between
analog input terminal and power supply/ground terminal
Vibration resistance
10 to 55Hz, 1 cycle/min: double amplitude of 0.75mm/ 0.030 in.,
10 min on 3 axes
Shock resistance Shock of 98 m/s
2
, 4 times on 3 axes
Noise immunity
1,000 Vp-p with pulse widths 50ns and 1μs (based on in-house
measurements)
Operating condition Free from corrosive gases and excessive dust
Weight Approx. 90g/3.175oz
Note
(
)For each additional A/D converter unit connected to a control unit,
the current consumption increases by 20mA (max.).