FP0 MEWNET-F Unit
Networking units
The FP0 can be used as a slave station for MEWNET-F (remote I/O system) by adding I/O link unit.
MEWNET-F is a reduced-wiring remote I/O system that connects PLCs
located separately and I/O slave stations with 2-core cabling. By adding an
I/O link unit to the FP0, you can link master station PLC and FP0 inputs and
outputs via the network.
Item Description
Communication method
Synchronous system
Two-wire, half duplex transmission
Start stop synchronous system
Transmission line 2-wire cable (Twisted-pair cable or equivalent to VCTF 0.75 mm
2
x 2C)
Transmission distance
(Total distance)
Max. 700m per port (using twisted pair cable)
Max. 400m per port (using VCTF cable)
Transmission speed (Baud rate) 0,5Mbit/s
Number of control I/O points
per an I/O link unit
64 points
(Input: 32 points and Output: 32 points)
Remote I/O map allocation
Interface
Transmission error check
32X/32Y
Conforms to RS485
CRC (Cyclic Redundancy Check) method
FP0-IOL Link Unit Specifications
By using C-NET, you can use multiple FP0s as data collection terminals.
By using the C-NET network and exclusive
adapters, you can connect multiple FP0s by
multi-drop connection with 2-wire cables.
You can use computers for separate control
or have network terminals for a centralized
management system.
MEWNET-F
C-NET