9-4
Setting for EHV-CPU128/EHV-CPU64/EHV-CPU32/EHV-CPU16
It should be specified with a programming tool.
Specify the setting for the serial port as below with a programming tool.
Item
Setting
Type
Special port
Port type *1
For RS232C connection: RS232C
For RS422 connection: RS422/485
For RS485 connection: RS422/485
Baud rate
19200bps
Communication procedure
Procedure 1 of transmission control (No unit No.) 1:1 communication
Unit No.
No unit No.
With modem connection
Not check
*1 It varies according to the communication method.
*2 For the details of the method of communication setting, refer to the "EH-150EHV series Ladder
Programming Software Control Editor Instruction Manual".
Setting for EH-SIO
Port 1 or Port 2
The setting for the dip switches and the ladder program to perform the default setting is required.
Specify as below with the dip switches for each port.
Item
Setting
Baud Rate
19200bps
Data Length
1
Parity Bit
Even
Stop Bits
7
Specify the setting for the communication port of EH-SIO with a ladder program as below.
Item
Setting
Default setting of communication mode
Hi-Protocol mode
Communication procedure
Procedure 1 of transmission control (No unit No.)
Unit No.
No
* For the details of the method of communication setting, refer to the "EH-150 Application Manual".