22
2-9
Blinking
indicator
Cancel
Auto address
1
Assigning
Display During Auto Address Setting
On the surface of outdoor unit control P.C. board
1
2
LED
Blinks alternately
* Do not short circuit the A.ADD pin again during auto address setting.
LEDs 1 and 2 go out and address setting is interrupted.
* When auto address setting is normally completed, both LEDs 1 and 2 go out.
In other cases, correct settings referring to the following table and perform auto address setting again.
Contents of LEDs 1 and 2 on outdoor unit control P.C. board
: ON : Blinking : OFF
LED1 LED2 Remark
Normal operation
Pre-trip (High pressure protection) LED1 Blinking : 0.8sec-ON / 0.3sec-OFF
Pre-trip (other)
LED1 Blinking : 0.5sec-ON / 0.5sec-OFF
Auto address
setting
Under auto address setting
Blinking alternately
Auto address setting alarm
Follow the blinking patterns of each alarm
Alternate blinking of outdoor unit LED
during alarms
LED1 blinks M times, and then LED2 blinks N times. The cycle then repeats.
M=2:P alarm, 3:H alarm, 4:E alarm, 5:F alarm, 6:L alarm, N=alarm No
Example: LED1 blinks 4 times, then LED2 blinks 6 times. The cycle then repeats. Alarm is “E06”
Power ON
sequence
No communication from indoor units in system
If it is not possible to advance to 3 repeats 1
2
Communication received from 1 or more
indoor units in system
At 3, advances to normal control
Regular communication OK
(Capacity and unit quantity match)
Refrigerant recovery mode
Display of remote controller
CZ-RTC5A / CZ-RTC5B CZ-RTC4
01_301769_2WAY_eng.indb 35 2018/3/20 9:15:14
2-9. Indicating (marking) the indoor and outdoor unit combination number
Indicate (mark) the number after auto address setting is completed.
So that the combination of each indoor unit can be easily checked when multiple units are installed, ensure that the indoor and
outdoor unit numbers correspond to the system address number on the outdoor unit control PCB, and use a magic marker or similar
means which cannot be easily erased to indicate the numbers in an easily visible location on the indoor units (near the indoor unit
nameplates).
Example: (Outdoor) 1 - (Indoor) 1
(Outdoor) 2 - (Indoor) 1
These numbers will be needed for maintenance.
Be sure to indicate them.
Use the remote controller to check the indoor unit address.
High-spec Wired Remote Controller (CZ-RTC5A / CZ-RTC5B)
(3) The “Simple settings” screen appears on the LCD display.
Select the “Unit no.” by pressing the
or
button for changes.
Simple settings
Unit no. Code no. Set data
01
3-1 0001
Sel. Next
20:30 (THU)
The indoor unit fan operates only at the selected indoor unit.
START
[]
20:30 (THU)
Timer remote controller (CZ-RTC4)
<If 1 indoor unit is connected to 1 remote controller>
(1) Press and hold the
button and
button for 4
seconds or longer (simple settings mode).
(2) The address is displayed for the indoor unit that is
connected to the remote controller.
( Only the address of the indoor unit that is connected to
the remote controller can be checked.)
(3) Press the
button again to return to normal remote
controller mode.
Number changes to indicate
which indoor unit is currently
selected.
Indoor unit address
(1) Keep pressing the ,
and buttons
simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the LCD
display.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel. Page [ ] Confirm
20:30 (THU)
(2) Press the or button to see each menu.
If you wish to see the next screen instantly, press the
or button.
Select “7. Simple settings” on the LCD display and press
the
button.
Maintenance func
5. Sensor info.
6. Servicing check
8. Detailed settings
Sel. Page [ ] Confirm
20:30 (THU)
7. Simple settings
01_301769_2WAY_eng.indb 36 2018/3/20 9:15:15