1-5-1
11 11
1-5. Capacity Correction Graph According to Temperature Condition
U-60PZ2R5 (For 50 Hz)
Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity)
Cooling Heating
Outdoor unit heating capacity correction cofficient during of frosting/defrosting (RH approximately 85%)
Outdoor intake air
temperature °C WB
-15-11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0123456
Correction coefficient
0.95 0.93 0.92 0.92 0.91 0.91 0.90 0.90 0.89 0.89 0.88 0.88 0.88 0.89 0.91 0.93 0.95 0.97 1.0
To calculate the heating capacity with consideration for frosting/defrosting operation, multiply the heating capacity
found from the capacity graph by the correction coefficient from the table above.
Capacity (kW)
0
20
40
60
80
100
120
140
160
180
Capacity (kW)
0
20
40
60
80
100
120
140
160
180
8642086420 10
135%
10
184%
200 200
22°CWB
19°CWB
16°CWB
16°CWB
19°CWB
22°CWB
40
60
80
100
120
140
Outdoor air intake temp ( °C DB)
Capacity coefficient (%)Input coefficient (%)Input coefficient (%)
Input coefficient (%)
40
60
80
100
120
140
-10 0 10 20 30 40-5 5 15 25 35
Indoor air intake temp ( °C WB)
Indoor air intake temp ( °C WB)
40
60
80
100
120
140
Outdoor air intake temp ( °C WB)
Capacity coefficient (%)
40
60
80
100
120
140
Indoor air intake temp ( °C DB)
Indoor air intake temp ( °C DB)
16°CDB
20°CDB
24°CDB
16°CDB
20°CDB
24°CDB
-15 -10 -5 0 5 10 15 20
Input coefficient (%)