45
14.14 Compressor Protection Control (Gas leak detection control 2)
This control detect gas leakage condition to prevent compressor damage.
Control start condition
o All connected indoor units capability supply ON.
o Compressor ON with maximum frequency.
o Not during annual cooling.
o Compressor discharge temperature high.
Control content
o Compressor OFF during this control (“F91” is memorized in EEPROM)
o If the above conditions happen 2 times within 60 minutes, indoor units’ Timer LED will blinks (“F91” is
indicated at all indoor units)
14.15 Valve close detection control
This control detects 3-way valve close condition to prevent damage to refrigerant cycle.
Start conditions:
o For all connected indoor units, if Indoor intake temperature — indoor piping temperature are between -2°C
and 2°C continuously for 5 minutes after compressor ON at first cooling operation.
o The first cooling operation is defined as cooling operation is ON for less than 8 minutes after new installation
or after pump down.
Control content
o During this control, compressor stop, indoor units’ Timer LED will blink. (“F91” is indicated at indoor units)
Error reset can be done by power supply reset or reset by using remote control.
14.16 Compressor discharge high pressure protection control
This control protect by using high pressure switch during operation.
Start conditions
o High pressure switch is activated (from normally close to open) when outdoor operation mode is cooling or
heating during compressor running.
Control 1 content
o Compressor stop when high pressure switch is opened and restart after high pressure switch closed. If this
condition happen 4 times within 30 minutes, “F94” is indicated.
o After 30 minutes, counter is reset if this condition does not happen for 4 times.
Control 1 stop conditions
o Power supply reset
o Reset by using remote control
14.17 Compressor discharge high temperature protection control
This control detect compressor discharge tube (CU-4Z68/3Z68/3Z52TBE)/compressor tank temperature
(CU-2Z35/41/50TBE) and perform the compressor frequency restriction.
CU-2Z35/41/50TBE CU-3Z52/3Z68/4Z68TBE
A 108°C 108°C
B 96°C 96°C
C 95°C 90°C
D 90°C 85°C
When the discharge temperature more than 108C, the compressor stops. If this condition happens for 3 times
within 30 minutes, “F97” is indicated.
Comp stop
108°C
95°C
96°C
90°C
Comp freq
restricted
Comp freq free
Comp disc temp (CU-4Z68/3Z68/3Z52TBE) o
Comp tank temp (CU-2Z35/41/50TBE)