SMARTZONE G5 INSTALLATION MANUAL
Grounding the PDU
Connecting the Ground Bonding Cable
There is an external ground bonding point located on the chassis of the PDU. The
ground bonding screw is provided as an attachment point for conductors. Use a ground
bonding cable if the rack contains any conductors for functional grounding or bonding of
ungrounded metal parts. This bonding point can also be used to bond the PDU to a
known earthed reference terminal in the building. Per international regulatory
requirements, the primary Safety Earth Bond connection is contained in the PDU as an
integral part of the branch circuit cabling and plug. The ground bounding point is located
on the surface with the receptacles on all PDUs except for the high-density models.
These models have the ground bounding point on the surface with the circuit breakers.