UL - Industrial Control Equipment for
Hazardous Locations
Suitable Equivalency
Area Classification -
Class I, Division 2
Groups A, B, C, D
Temperature Classification - T3
Area Classification -
Temperature Classification - T3
Electrical System
For use in 1 and 3-phase AC systems
Voltage Detection Range
Up to 600V AC (50/60Hz), 600V DC; Rated tolerance +10%
Absence of Voltage Threshold
3 V (See the Installation Considerations section for additional information)
Overvoltage Category
III (600 V)
Degree of Protection*
Indicator Module: For Flat Surface Mounting in a TYPE (UL, NEMA and CSA) 1, 12, 4, 4X,
13, IP66, or IP67 Enclosure
Isolation Module: Open Type, IP20
*Degree of protection specified is related to the Indicator Module only. To meet the TYPE (UL, NEMA and CSA) 1, 12, 4, 4X, 13, IP66 or IP67
requirements, mount on a flat surface of an enclosure meeting the appropriate UL TYPE or NEMA rating. Verify that the seal and o-rings are
clean to ensure proper sealing.
Operating Temperature
0°C to 60°C (32°F to 140°F)
Storage Temperature
-45°C to 85°C (-49°F to 185°F)
Humidity
5 to 90% non-condensing; Rated 80% at 40°C, decreasing linearly to 50% at 60°C
Pollution Degree
3
Altitude
Up to 2000 meters (1.24 miles)
Type
Industrial 3.6V Lithium AA, see table in Maintenance section for list of compatible batteries.
Functional Safety
Supported Safety Integrity
Levels
Error Handling Response Time