Fighter - Advanced Analogue Conventional Fire Alarm & Extinguishing Control Panel
support telephone number and/or other means of communication in case the installer
must be contacted. The contents of this screen are programmed at A.L.3 menu item
|8.Additional Options|.
4. Access Level 2 (A.L.2)
The items of the A.L.2 menu is as follows:
Evacuation Start1.
Bypass Zones2.
Bypass Relays3.
User's code4.
Zone descriptions5.
Periodic Test6.
Time/Date Adj.7.
Walk Test8.
9. Intellizone Cancel
Pressing < > on some screens will display a help screen with useful related informa-
tion.
Press [ACC] button to enter access level 2: Access Code Prompt is displayed.
Enter a valid PIN: Access Level 2 menu is displayed.
4.1 Evacuation (ALM2.1)
To activate the evacuation procedure:
Press <1> for menu item |1.Evacuation start|: Setting for the evacuation proce-
dure are displayed.
Press <ENTER> to conrm the evacuation or <CLR> to cancel the evacuation.
EVACUATION
————————————————————
ENTER to confirm
CLR to return
Figure 12. Set global evacuation from keypad screen
4.2 Zone Bypasses (Zone disablements) (ALM2.2)
To activate a bypass on a zone:
Press <2> to select menu item |2. Bypass Zones|: The list with all available zones
is displayed (see Figure 13).
Use <Up> <Down> keys to place the ashing cursor on the required zone.
Use the <Right Arrow> to activate a bypass and <Left Arrow> to cancel a by-
pass.
Once nished press <CLR> to exit access level 2 menu.