Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D Page D-191
8
9
10
11
B
C
D
1
2
3
4
5
6
7
E
111.06 ACTIVE PHASE TUNING BOOL 0 : FALSE
1 : TRUE
FALSE ro Output
111.08 REFERENCE TYPE PHASE TUNING ENUM 0 : SQUARE
1 : SINUSOIDAL
2 : TRIANGULAR
SQUARE rw
111.09 SPEED AMPLITUDE PHASE TUNING REAL 0.0000 to 100.0000 rev/s 0.1000 rev/s rw
111.12 RUN TR FUNC TEST PHASE TUNING BOOL 0 : FALSE
1 : TRUE
FALSE rw
111.13 NO OF
MEASRMENTS
PHASE TUNING INT 1 to 10000 100 rw
111.14 TORQUE
AMPLITUDE
PHASE TUNING REAL 0.00 to 100.00 % 20.00 % rw
111.15 TRANSF FUNC TYPE PHASE TUNING ENUM 0 : SPEED TRANSFR FN
1 : OPEN LP TRANS FN
OPEN LP
TRANS FN
rw
111.16 POS'N AMPLITUDE PHASE TUNING REAL 0.0000 to 100.0000 deg 1.0000 deg rw
111.17 MEASURMENTS
DONE
PHASE TUNING INT _ 0 ro Output
112.01 ENABLE POWER LOSS CNTRL BOOL 0 : FALSE
1 : TRUE
FALSE rw
112.02 TRIP THRESHOLD POWER LOSS CNTRL REAL 0 to 1000 V 447 V rw 3,5
112.03 CONTROL BAND POWER LOSS CNTRL REAL 0 to 1000 V 20 V rw
112.04 ACCEL TIME POWER LOSS CNTRL REAL 0.01 to 300.00 s 10.00 s rw
112.05 DECEL TIME POWER LOSS CNTRL REAL 0.01 to 300.00 s 5.00 s rw
112.06 TIME LIMIT POWER LOSS CNTRL REAL 0.00 to 300.00 s 30.00 s rw
112.07 PWR LOSS ACTIVE POWER LOSS CNTRL BOOL 0 : FALSE
1 : TRUE
FALSE ro Output
112.08 INITIAL STEP POWER LOSS CNTRL REAL 0.00 to 100.00 % 0.00 % rw
113.01 RESET ENERGY METER BOOL 0 : FALSE
1 : TRUE
FALSE rw
113.02 POWER ENERGY METER REAL _.xx 0.00 kW ro Output
113.03 POWER ENERGY METER REAL _.xx 0.00 hp ro Output