H Series Fieldbus PROFIBUS Adapter, Series A (PSSCPBA) E102P
5
Wire the PROFIBUS Adapter
Following are wiring instructions for the PROFIBUS Adapter.
Make sure all connectors and caps are securely tightened to
properly seal the connections against leaks and maintain IP67
requirements.
!
ATTENTION
Male In Connector
PSSCPBA(MicroM12,B-CodingReverseKey)
(view into connector)
Pin 1 - +5VBUS
Pin 2 - A-Line
Pin 3 - GNDBUS
Pin 4 - B-Line
Pin 5 - Not Used
Male In Connector
PSSCPBA Male Auxiliary (Mini 7/8")
(view into connector)
Pin 1 - User Power -
Pin 2 - Adapter Power -
Pin 3 - Protective GND
Pin 4 - Adapter Power +
Pin 5 - User Power +
Note: Please refer to page 3, Mount the Adapter
and I/O Base, for shielding information.
NOTE: User power is the 24VDC power for field devices.
Adapter power is the 24VDC power for adapter. It is converted to
5VDC to power H Series Fieldbus modules.