Publication PSS-UM001A-EN-P – December 2016
Default Data Maps B-3
PSSNAV Analog Voltage Input Module
Message size: 6 Bytes
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Produces (scanner Rx) Input Channel 0 - High Byte Input Channel 0 - Low Byte
Input Channel 1 - High Byte Input Channel 1 - Low Byte
Status Byte for Channel 1 Status Byte for Channel 0
OR UR HHA LLA HA LA CM CF OR UR HHA LLA HA LA CM CF
Consumes (scanner Tx) No consumed data
Where: CF = Channel Fault status; 0 = no error, 1 = fault
CM = Calibration Mode; 0 = normal, 1 = calibration mode
LA = Low Alarm, 0 = no error, 1 = fault
HA = High Alarm; 0 = no error, 1 = fault
LLA = Low/Low Alarm; 0 = no error, 1 = fault
HHA = High/High Alarm; 0 = no error, 1 = fault
UR = Underrange; 0 = no error, 1 = fault
OR = Overrange; 0 = no error, 1 = fault
PSSTAC Analog Current Output Module
Message size: 4 Bytes
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Consumes (Tx) Output Channel 0 High Byte Output Channel 0 Low Byte
Output Channel 1 High Byte Output Channel 1 Low Byte
Message size: 2 Bytes
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Produces (Rx) High Byte - Channel 1 Status Low Byte - Channel 0 Status
Not Used HCA LCA CM CF Not Used HCA LCA CM CF
Where: CF = Channel Fault status; 0 = no error, 1 = fault
CM = Calibration Mode; 0 = normal, 1 = calibration mode
LCA = Low Clamp Alarm, 0 = no error, 1 = fault
HCA = High Clamp Alarm; 0 = no error, 1 = fault