H Series Fieldbus 24 VDC Output Modules, Series A E107P
8
Digital Output Modules
Outputs per Module 8 (1 Group of 8) Non-isolated, Sourcing 16 (1 Group of 16) Non-isolated, Sourcing
Voltage Drop, On-State Output, Maximum 0.2VDC (Sourcing Modules)
0.7VDC (Sinking Module)
Voltage, Off-State Output, Maximum 28.8VDC
Voltage, On-State Output,
Maximum
Minimum
Nominal
28.8VDC
10VDC
24VDC
Current Leakage, Off-State Output, Maximum 0.5 mA
Current, On-State Output Minimum 1.0 mA Per C hannel
Output Current Rating 1.0 A Per Channel, Not To Exceed 3.0 A Maximum Per Module
Output Delay Time OFF to ON, Maximum
1
0.1 ms
Output Delay Time, ON to OFF, Maximum
1
0.1 ms
Output Point Density 8 or 16
Output Surge Current, Maximum 2 A for 10 ms, Repeatable Every 3 Seconds
External DC Power Supply Current 32 mA
External DC Power Supply Voltage Range 10 to 28.8VDC
External DC Power Supply Voltage Nominal 24VDC
KeyswitchPosition 1
LED Indicators 8 orr 16 Yellow/Red Output Status, Logic Side
1 Green/Red Network Status, Logic Side
1 Green/Red Module Status, Logic Side
PointBus Current, Maximum 75 mA @ 5VDC
Power Dissipation, Maximum PSST8M-2.0W@28.8VDC
Thermal Dissipation, Maximum PSST8M - 6.8 BTU/hr. @ 28.8VDC
Isolation Voltage
(continuous-voltage withstand rating)
50V rms
Tested at 1250VAC rms for 60s
Dimensions (includes I/O module Inches
and mounting base) (Millimeters)
4.72Hx2.82Wx1.65D
(120Hx72Wx42D)
Operating Temperature IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20 to 60°C (-4 to 140°F)
Storage Temperature IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
-40 to 85°C (-40 to 185°F)
Relative Humidity IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):
5 to 95% Non-condensing
Shock IEC60068-2-27 (Test Ea, Unpackaged Shock):
Operating 30g
Non-operating 50g
Vibration IEC60068-2-6 (Test Fc, Operating):
5g @ 10 to 500Hz
ESD Immunity IEC 61000-4-2:
6kV Contact Discharges
8kV Air Discharges
Radiated RF Immunity IEC 61000-4-3:
10V/m with 1kHz Sine-wave 80% AM from 30MHz to 2000MHz
10V/m with 200Hz 50% Pulse 100% AM at 900Mhz
10V/m with 200Hz 50% Pulse 100% AM at 1890Mhz
EFT/B Immunity IEC 61000-4-4: ±3kV at 5kHz on Signal Ports
Surge Transient Immunity IEC 61000-4-5: ±1kV Line-line(DM) and ±2kV Line-earth(CM) on Signal Ports
Conducted RF Immunity IEC 61000-4-6: 10Vrms with 1kHz Sine-wave 80%AM from 150kHz to 80MHz
Emissions CSPR 11: Group 1, Class A
Enclosure Type Rating Meets IP65/66/67 (when marked)
Mounting Base Screw Torque #8 Screw, 7.5 in. lbs. in Aluminum, 16 in. lbs. in Steel
WiringCategory
2
1 - on Signal Ports
WeightImperial(Metric) 0.64 lb. (0.29 kg)
Certifications:
(when product is marked)
c-UL-us UL Listed Industrial Control Equipment,
certified for US and Canada
CE European Union 89/336/EEC EMC Directive, compliant with:
EN 61000-6-4; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
C- Tick Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11;
Industrial Emissions
1. OFF to ON or ON to OFF delay is time from a valid output “on” or “off” signal to output energization or de-energization.
2.UsethisConductorCategoryinformationforplanningconductorrouting.RefertoPublicationE115P,“IndustrialAutomationWiringandGroundingGuidelines”.
Specications -
Following are specifications for the digital output modules.