Parker Hannifin S.p.A. – S.B.C. Division quick installation guide Hi-drive
Page 3 of 12
1.1 Hardware specifications
Description Symbol UdM Type of drive
Hi-Drive type 2 5 8 16 25
POWER
Mains supply: three-phase or single-phase or D.C.
Three-phase rated voltage V
mains
V~
200 – 10% $ 480 +10%
Single-phase rated voltage V
mains
V~
200 – 10% $ 277 +10%
D.C. V
dc
V=
245 $ 744
Frequency of the A.C. supply f
mains
Hz 50…60 ±5%
Load installed for continuous service S KVA 1,4 3,5 5,6 11,2 17,5
PWM switchover frequency
(selectable)
f
sw
kHz 8-16 8
PWM switchover frequency (default) f
def
kHz 8
Continuative current at output (*) ±2% I
cont
Arms 2 5 8 16 25
Peak current at output 2s (*) ±2%
I
peak
Arms 4 10 16 32 50
Current derating in case of f
sw
>f
def
Kf p.u. 0,7 -
Current derating @ 480V
mains
Kv p.u. 0,9
Maximum frequency at output f
out
Hz 0÷500
Power stage losses Ploss W 30 75 120 220 350
Volumetric capacity of internal fans Q m
3
/h 32 47 63 168 168
Braking resistance Rb Ohm 200 90 75 40 27
Continuous internal braking power Pb
cont
W 75 75 120 180 180
Braking power peak 790VDC Pb
peak
W
s
3120
1
6935
0,7
8320
0,5
15600
0,2
23115
0,15
Continuative power P
out
W See diagrams
Overvoltage cutout (OV) V
ovl
V 870
Undervoltage cutout (UV) V
und
V 70% * 2 *V
mains
CONTROL
D.C. power supply Vcc V= 24 (0%…+10%)
Maximum ripple Vcc
ripple
V Do not exceed range
Max power input Icc A= 2
Power input Pcc W 30
PARKING BRAKE
Power supply voltage Vs V= 24 ±10%
Max current Is A= 2
(*) data applied according to the default switchover frequency and 400 V power voltage; higher values derate the
output current.
2 INSTALLATION
2.1 Identification
Five available models: HID2, HID5, HID8, HID16 and HID25, where the number corresponds to the rated
current (in A) which the drive can dispense.
This is a product of the restricted sales distribution class
according to EN61800-3.
In a domestic environment this product may cause radio
interference in which case the user may be required to
take adequate measures.
The installation and cabling operations must be done
when there is absolutely no voltage in the entire electric
cabinet. Make sure that the power switch on the converter
is cut off from the emergency circuit. The first time the
cabinet is powered up, qualified technical personnel must
be present.
This symbol is an invitation to refer to the more detailed information in the
integral version of the operator's manual attached to the supply or which
can be downloaded from www.sbcelettronica.com