Parker Hannifin S.p.A.  - S.B.C. Division                                               HPD N User’s Manual 
 
31
Pr5 Internal reference. Unit=rpm, range=±9000, default=0. If b40.12=1 and b40.13=0, 
Pr7 will be the same as Pr5. 
Pr6  Reserved read-only speed reference. Unit=rpm, range=±9000. If b40.2=1 Pr6 is 
only utilised as a speed reference for the control loop. The active operating mode will 
enter its speed request in parameter Pr6. 
Pr7 Main reference (read-only parameter). Unit=rpm, range=±9000. If b40.2=0, Pr7 is 
used as a reference for the speed control loop. In certain operating modes Pr7 can be 
used as a reference for other factors (torque / acceleration). In this case Pr7 is 
expressed in a suitable unit. 
Pr8  Acceleration ramp for positive speed values. Unit=s/krpm range=0.002..65.535, 
resolution=0.001 s, default=0.002 s. Acceleration for positive speeds required of the 
motor by way of the speed reference is internally limited so that acceleration of 1000 
rpm takes Pr8 seconds. 
Pr9  Deceleration ramp for positive speed values. Unit=s/krpm, range=0.002..65.535, 
resolution=0.001 s, default=0.002 s. Deceleration for positive speeds required of the 
motor by way of the speed reference is internally limited so that deceleration of 1000 
rpm takes Pr9 seconds. 
Pr10  Acceleration ramp for negative speed values. Unit=s/krpm, range=0.002..65.535, 
resolution=0.001 s, default=0.002 s. Acceleration for negative speeds required of the 
motor by way of the speed reference is internally limited so that acceleration of 1000 
rpm takes Pr10 seconds. 
Pr11  Deceleration ramp for negative speed values. Unit=s/krpm, range=0.002..65.535, 
resolution=0.001 s, default=0.002 s. Deceleration for negative speeds required of the 
motor by way of the speed reference is internally limited so that deceleration of 1000 
rpm takes Pr11 seconds. 
 Pr12  Deceleration ramp for stroke end and stop functions. Unit=s/krpm, 
range=0.002..65.535, resolution=0.001 s, default=0.002 s. Deceleration required of 
the motor by the stroke limit and stop functions is internally limited so deceleration 
of 1000 rpm takes Pr12 seconds. 
Pr13 Overspeed threshold. Unit=rpm, range=0..+13000, default=3500. If the absolute 
value for motor speed exceeds the value entered in Pr13, b41.0 must be =1, otherwise 
it will be = 0. 
Pr14  High speed threshold. Unit=rpm, range=±13000, default=20. When b40.7=0, if the 
speed difference between motor and reference is less than Pr14 and greater than 
Pr15, b41.1 will be =1, otherwise it will be = 0. In the case of b40.7=1, if motor 
speed is less than Pr14 and higher than Pr15, b41.1 will be =1, otherwise it will be 
=0. 
Pr15 Low speed threshold. Unit=rpm, range= ±13000, default=20. When b40.7=0, if the 
speed difference between motor and reference is less than Pr14 and greater than 
Pr15, b41.1 will be =1, otherwise it will be =0. In the case of b40.7=1, if motor speed 
is less than Pr14 and higher than Pr15, b41.1 will be =1, otherwise it will be =0. 
Pr16  Integral gain of speed control loop. Range =0...32767, default=120. 
Pr17  Speed control loop damping. Range=0...32767, default=2000. If Pr16 is set to zero 
Pr17 sets the value for proportional gain of the speed control loop. 
Pr18 Bandwidth limiter. Unit=512μs, range=0..1000, default=1. Use Pr18 to set the time 
constant of a first order filter located on the digital torque demand signal. The filter 
cut-off frequency will be: 310/Pr18 Hertz.