EasyManua.ls Logo

Parker PA Series - Technical Specifications

Parker PA Series
30 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 3
Technical Specifications
Environmental Specifications
Ambient temperature: 32~140 (0~60 °C)
Protection class: IP66
Vibration resistance parameter: 100Hz
Electrical Specifications
Connections: cable gland
Supply voltage:
24 V DC ± 10 %, ≥1A. Recommend switching-mode power supply.
Power input: <5W
Input resistance for set-point signal: 12
Analog output signal: maximum load 560Ω
Mechanical Specifications
Cover material: Polycarbonate (PC)
Sealing material: Silicone rubber (SI)
Main body material: Polyamide Resin (PA6-GF30)
Control stroke range: 0.196-0.98 in (5-25 mm)
Pneumatic Specifications
Pilot air supply range: 43.5~101.5 psi (3~7 bar), specific values
depending on the actuator
Connections: Plug-in hose connector G1/4
Air quality:
Clean dry air, according to ISO 8573-1;
Maximum particle density 10 mg/ ;
Maximum particle size 40 micron;
Maximum oil content 25 mg/m³;
Maximum pressure dew point -4 (-20 °C) or minimum 50 (10
°C) below the lowest operating temperature.;
Air flow rate: 0.60 scfm (17L/min) (input pressure of 87 psi
(0.6Mpa)).

Other manuals for Parker PA Series

Related product manuals