PSE 120-350
Modbus
Choose your options. MODBUS RTU (RS485)
Touch
to go ahead. MODBUS TCP/IP
Choose your options.
Touch
to go ahead.
Choose your options.
Switch off /switch ON the dryer
to confi rm
Condensate drain
Touch to enter.
Touch as indicated to choose the type of the drain:
0 = external;
1 = timed;
2 = capacitive.
in the case of the choice of the timed discharger (1) it is also possible to choose the closing and ope-
ning times “D1 / D2”.
Maintenance
Touch to enter.
these data are read-only.
Parity: 0=NONE; 1=ODD: 2=EVEN;
Baud rate
0 9600 3 57600
1 19200 4 76800
2 38400 5 115200
PARAMETER Code Default
Unit address CF30 16
Baud rate CF31 19200
Parity CF32 2