Messages, errors and error handling
56
Error description /
message on display
Reason
Reaction
Control / Action
Error sensor 1
Sensor break or short circuit
temperature sensor T1
Fans are turned off
Check or replace sensor
Error sensor 2
Sensor break or short circuit
temperature sensor T2
Fans are turned off
Check or replace sensor
Error sensor 3
Sensor break or short circuit
temperature sensor T3
Fans are turned off
Check or replace sensor
Error sensor 4
Sensor break or short circuit
temperature sensor T4
Fans are turned off
Check or replace sensor
Supply air temperature
too low
Minimum supply air
temperature < setpoint;
Factory setting 5 °C
Fans are turned off
Supply air temperature
> setpoint + 1 K
Intake air temperature
too low
Current intake air
temperature < setpoint
longer than 10 minutes
Fans are turned off
Intake air temperature
> setpoint;
control after 1 h
Error fan 1 Hall
Supply air fan speed does
not report
Fans are turned off
manual adjustment of
an speed
Error fan 2 Hall
Exhaust air fan speed does
not report
Fans are turned off
manual adjustment of
an speed
Communication error
BUS components of the
controller are not detected
Fans are turned off
Restart (Off / On) of the
device
No external release
Release contact open
Fans are turned off,
no control by external
control unit
Close release contact
Table 4: Overview of messages, error visualisation and error treatment by means of the TFT touch panel