| VSP
CONF.GROUP
NO COM
WORKING MODE FOR LACK OF COMMUNICATION BETWEEN PARALLEL VSP
Conguration and choice of VSP parallel operating mode if no commu-
nication and/or one of the two VSP has a fault.
STOP=the VSP stops in the event of no communication.
SOLO=the VSP continues to work as if a single, independent VSP.
Default STOP Range STOP – SOLO
SELECT
TEST
Electric pump TEST mode
9
TEST
PREX 0,0
SYSTEM PRESSURE
Read only parameter of system pressure
TEST
FREQ 0,0
SYSTEM FREQUENCY
Motor power supply frequency change
Default 30 Hz Range 30-50 Hz Step 1 Hz
TEST
CURRENT 0,0
MOTOR CURRENT
Read only parameter of motor current
TEST
COSFI 0,0
MOTOR COSFI
Read only parameter of cos motor
TEST
TEMP. MOD 20
POWER MODULE TEMPERATURE
Read only parameter of inverter module temperature
TEST
VOLTAGE 225
POWER SUPPLY VOLTAGE
Read only parameter of inverter power supply voltage
SELECT
RESTORE DEF
9
RESTORE DEF
CONFIRM?
LOAD DEFAULT PARAMETERS
This menu allows you to reset the VSP parameters if the client wants
to restore the values by returning to the initial default conguration.
Default No Range Yes–No