PLUS 200 2 PLT
Page 16
Rev. 02-06
MANUALE D’USO E MANUTENZIONE
LEVEL 2 PROGRAMMING (Installer level)
To access the second programming level press the UP (t) and DOWN (u) keys and the
LIGHT key simultaneously for a few seconds.
When the first programming variable appears the system automatically goes to stand-by.
1. Select the variable to be modified by pressing the UP (t) and DOWN (u) keys.
When the parameter has been selected it is possible to:
2. View the setting by pressing the SET key.
3. Modify the setting by holding the SET key down and pressing the (t) or (u) key.
VARIABLE MEANING VALUES DEFAULT
tEu
Displays evaporator sensor temperature / current
day-date
0 = current day
1 = displays
evaporator 1
temperature;
displays nothing if
dE =1
2 = displays
evaporator 2
temperature;
displays nothing if
dE2 =1
0
dF1
Real-time defrost enable, evaporator 1
With dF1=1 it is possible to set up to 6 defrosts in real
time in a day by using the parameters d41…d46
0 disabled
1 enabled
0
dF2
Real-time defrost enable, evaporator 2
With dF2=1 it is possible to set up to 6 defrosts in real
time in a day by using the parameters d51…d56
0 disabled
1 enabled
0
d41…d46
Programming defrost times, evaporator 1
It is possible to set up to 6 defrosting times
00:00:00 -
23:50:00
--
d51…d56
Programming defrost times, evaporator 2
It is possible to set up to 6 defrosting times
00:00:00 -
23:50:00
--
CHAP. 5 - Parameter programming