PLUS 200 2 PLT
Page 18
Rev. 02-06
MANUALE D’USO E MANUTENZIONE
Ad
Network address for connection to the
TeleWIN supervision system
0 – 31 0
Ald
Minimum and maximum temperature
signalling and alarm display delay
1…240 min 2:00:00
C1
Minimum time between shutdown and
subsequent switching on of the
compressor.
0…15 min 0 min
Hr1
Compressor 1 hour counter (can be
reset by pressing the set and clock keys
for 10 sec)
0-999 tens of hours 0
Hr2
Compressor 2 hour counter (can be
reset by pressing the set and clock keys
for 10 sec)
0-999 tens of hours 0
CAL
Room sensor value correction
-10…+10 0
Pc1
Compressor 1 protection contact status
0 = NO
1 = NC
0 = NA
Pc2
Compressor 2 protection contact status
0 = NO
1 = NC
0 = NA
doC
Compressor safety time for door
switch: when the door is opened the
evaporator fans shut down and the
compressor will continue working for time
doC, after which it will shut down.
0…5 minutes 0
Fst
FAN shutdown TEMPERATURE
The fans will stop if the temperature value
read by the evaporator sensor is higher
than this value.
-45…+45°C +45°C
tA
NO – NC alarm relay switching
=activates when alarm is on
1=deactivates when alarm is
on
1
rA
Control relay door anti-fogging element
0=alarm relay
1=anti-fogging element on
0
int
Spare
------ --
dMY
Day-month-year setting
dd-mm-yy -
hMS
Clock setting
Hour-min-sec -
CHAP. 5 - Parameter programming