Screen Features
Home Screen
Figure 10 - Home Screen
The Home screen is always displayed unless the control
settings are being configured or during regeneration. This
screen displays general information about the system and
allows you to start a manual regeneration or access control
settings. Features of the screen are described below, followed
by more detailed information about each feature.
NOTE: If no button is pushed for five minutes, the screen will
enter a power save mode. The unit will continue to
operate, but the screen will be blank. Touch anywhere
on the screen to exit power save mode.
• Regeneration: Press to start a manual regeneration.
• Settings: Press to access commonly used settings.
• Diagnostics: Press to view diagnostic data.
• Assistance: Press to display the name and phone number
to call for service.
• Vacation Mode: Press to halt all scheduled regenerations;
press again to resume normal operation.
• Regeneration Cycle Wheel: Displays the cycle steps the
valve will step through during a regeneration; the current
cycle step is always at the top of the wheel.
• Treatment: The unit is treating water
• Backwash: Water flows from the bottom of the vessel
to the top of the vessel to clean the media
• Draw: Brine is drawn into the media and then slowly
rinsed out
• Rinse: Water flows from the top of the vessel to the
bottom of the vessel to rinse the media
• Refill: Brine tank is refilled with water
• Next Scheduled Regeneration: Displays the time to
next scheduled regeneration, or volume remaining until
regeneration in meter systems.
Day and Time
Regeneration
Settings
Regeneration
Cycle Wheel
Next Scheduled
Regeneration
Current Cycle
Step
Diagnostics
Assistance
• Day and Time: Displays the currently programmed day of
the week and time. This button will flash if the control has
been reset.
Regeneration
Regenerate the system on demand by pressing the
Regeneration button on the home screen. Manual Regeneration
can only be used while the valve is in the treatment position.
From the Home screen, press the Regeneration button . The
Regeneration screen appears.
Figure 11 Regeneration Screen
• Press now to begin a regeneration immediately, or
press at regen. time to queue the regeneration for the
programmed regeneration time (2:00 AM default for
softeners, 12:00 AM default for filters). Pressing at regen.
time again will cancel the manual regeneration.
• During Regeneration, press the button to immediately
advance to the next cycle step. Once in regeneration, the
volume or time will be displayed below the button.
Day and Time
From the Home screen (displayed in Figure 10 above) press the
Day and Time button. The Day and Time screen appears.
Figure 12 Day and Time Screen
• Press the Day of Week, Hour, Minute, and AM/PM/HR
buttons to adjust the values to the correct day and time.
Setting the value of the AM/PM/HR button to HR changes
the display to a 24 hour clock. Press the Day, Month, and
Year buttons to adjust the values to the correct date.
Press the button when finished to return to the Home
screen.
Return
to Home
Screen
Month
Day
Day of Week
Minute
Hour
AM/PM/HR
Year
TOUCHSCREEN CONTROL FEATURES
continued
Vacation
8 • FLECK 5810 & 5812 XTR2 Service Manual