IDENT-I • IVI-KHA6-4HRX, IVI-KHD2-4HRX
Basic operating modes
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
epperl+Fuchs Group • Tel.: Germany (06 21) 7 76-0 • USA (330) 4 25 35 55 • Singapore 7 79 90 91 • Internet http://www.pepperl-fuchs.com
Date of issue 27.08.2001
9
4 Basic operating modes
This control interface unit can be configured to operate either as a fixed code control
interface unit or as a read/write control interface unit. The operating mode is selected
by means of DIP switches S4, S5 and S6, located on the top of the unit.
When configured in fixed-code mode, this interface unit is software compatible with
the IRI-KHA6-4HRX and IRI-KHD2-4HRX control interface unit units.
By some kind of switches, the description of the switch-setting "open" corresponds
with "OFF" or "0". The switch-setting "close" corresponds with "ON" or "1".
Basic operation mode S4 S5 S6
Fixed Code open open open
Read/write open close close
3964R with RK512 Interpreter open close open
3964R without RK512 Interpreter close open open
Switch settings which have not been defined should not be used.