AS-Interface
Appendix: AS-i Slave Lists and Data Telegrams
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group · Tel.: Germany (621) 776-0 · USA (330) 4253555 · Singapore 7799091 · Internet http://www.pepperl-fuchs.com
issue date 12.10.1999
54
82
hex
: Upload
The information about the reading and the writing of the AS-i Control flags is deposit-
ed in place of address byte 0. Address byte 1 and all data bytes are set to the value
00
hex
.
Coding Read AS-i Control flags (00
hex
)
Coding Write AS-i Control flags (80
hex
)
address byte 0 = flags
Example: Starting the AS-i Control program in the AS-i/PROFIBUS Gateway:
(Ignore_config_errors = no, Auto_Start = no, Map_Counters = no)
DP-request: 80
hex
01
hex
00
hex
00
hex
... 00
hex
Coding Download (81
hex
)
state:00hexdownload successful
state:FFhexerror during download
byte 0 byte n
DP-request 00
hex
00
hex
00
hex
00
hex
... 00
hex
DP-responset 00
hex
Flags ...
byte 0 byte n
DP-request 80
hex
Flags 00
hex
00
hex
... 00
hex
DP-response 80
hex
Flags ...
address byte 0 = flags
bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
start/stop
DP-request: 0-->1 transition:
reset of AS-i control program
DP-response: 0
Ignore_config_errors
Auto_Start
Map_Counters
0
0
DP-request: 0
DP-response: AS-i control program running
byte 0 byte n
DP-request 81
hex
B0 B1 D0 ... Dn
DP-response 81
hex
B0 B1 State 0 0