5.10 Phase sequence adjustment
5.10.1 Manual phase sequence adjustment
The user can adjust the phase sequence of the current channel corresponding to
the voltage channel according to the field wiring;
5.10.2 Automatic phase sequence adjustment
The phase sequence can be adjusted automatically by one-key operation through
the meter interface.
[Note] The automatic phase sequence adjustment needs to meet the following
conditions: Under normal working conditions, the wiring mode is three-phase
three-wire mode and the A/B/C three-phase power factor is greater than 0.8;
Chapter 6 Input-output characteristics
6.1 Switch value input
EGO700 comes standard with 1-way active switch value input, which is suitable
for monitoring status information of circuit breaker and switch. External active switch
value.
When the external node is closed, the switch input is displayed as closed, and the
internal state information is set to 1; when the external node is disconnected, the
switch input is displayed as opening, and the internal state information is set to 0.