Conventional thermal
current while loading
several contacts
774140 774141 774142
Ith per contact at UB AC
AC1:400V
Conv. therm. current
with 1 contact 5 A 5 A 5 A
Conv. therm. current
with 2 contacts 5 A 5 A 5 A
Conv. therm. current
with 3 contacts 5 A 5 A 5 A
Conv. therm. current
with 4 contacts
5 A 5 A 5 A
Conv. therm. current
with 5 contacts 5 A 5 A 5 A
Conv. therm. current
with 6 contacts 5 A 5 A 5 A
Conv. therm. current
with 7 contacts 4,8 A 4,8 A 4,8 A
Conv. therm. current
with 8 contacts 4,5 A 4,5 A 4,5 A
Times 774140 774141 774142
Switch-on delay
With automatic start
typ. 25 ms 25 ms 25 ms
With automatic start
max. 40 ms 40 ms 40 ms
With automatic start
after power on typ. 50 ms 50 ms 50 ms
With automatic start
after power on max. 70 ms 70 ms 70 ms
Delay-on de-energisation
With E-STOP typ. 20 ms 20 ms 20 ms
With E-STOP max. 30 ms 30 ms 30 ms
With power failure typ. 220 ms 220 ms 220 ms
With power failure max. 300 ms 300 ms 300 ms
Supply interruption before
de-energisation 150 ms 150 ms 150 ms
Environmental data 774140 774141 774142
Climatic suitability EN 60068-2-78 EN 60068-2-78 EN 60068-2-78
Ambient temperature
Temperature range -10 - 55 °C -10 - 55 °C -10 - 55 °C
Storage temperature
Temperature range -40 - 85 °C -40 - 85 °C -40 - 85 °C
Climatic suitability
Humidity 93 % r. h. at 40 °C 93 % r. h. at 40 °C 93 % r. h. at 40 °C
Condensation during op-
eration Not permitted Not permitted Not permitted
EMC EN 60947-5-1, EN
61000-6-2, EN 61326-3-1
EN 60947-5-1, EN
61000-6-2, EN 61326-3-1
EN 60947-5-1, EN
61000-6-2, EN 61326-3-1