SECTION 2 – INSTALLATION DETAILS
2.1 INSTALLATION CHECKLIST
WARNING
Do NOT apply power to the LC1000 until its installation has been checked and
found to be in accordance with these instructions; National Electric Code;
Federal, State and Local codes; and other applicable safety codes. FAILURE TO
COMPLY MAY RESULT IN PERSONAL INJURY, PROPERTY LOSS AND
EQUIPMENT DAMAGE.
The following points should be reviewed in preparation for installation, and again when installation
is complete.
1. Review Figures 3-2 and/or 3-3 to ensure that all of the safety/wiring requirements have been
met.
2. Check that all equipment at job site matches the DESIGN DRAWING SPECIFICATIONS for
the tank sizes and control features required.
3. The console should be located as close as possible to the demarcation point of the hazardous
area. Never mount inside the hazardous area. Note: If the LC1000 was provided with a
NEMA 7 Explosion-proof enclosure, then it is permitted to install the LC1000 in the hazardous
location provided that all fittings and conduit are explosion-proof and all applicable regulations
are followed.
4. POWER to the console should be properly wired to a DEDICATED 120 VAC CIRCUIT
BREAKER. No other equipment can be powered from the same circuit breaker as the LC1000.
5. System cannot be connected to equipment that uses or generates more than 250 volts with
respect to earth.
6. All LC1000 grounds must be terminated at the GND BUSS BAR in the same service panel as
LC1000 power. A grounding rod, coldwater pipe or other connection should not be used.
7. Do not drill or modify enclosure. Use only conduit entries provided. Failure to comply will
void warranty and may present a safety hazard.
8. WATERPROOFING FIELD WIRE SPLICES using factory supplied splice kits is required for
proper system operation.